1) Select the inverter according to the load characteristics. If the load is a constant torque load, select the siemensMM420/MM440 inverter. If the load is a fan or a pump, the MM430 inverter should be selected.
2) When selecting the inverter, the actual current value should be used as the basis for the inverter selection. The rated power of the motor can only be used as a reference. In addition, it should be fully considered that the output of the inverter is rich in high-order harmonics, which will deteriorate the power factor and efficiency of the motor. Therefore, when the inverter is used to supply power to the motor and the power supply is supplied by the power frequency grid, the current of the motor will increase by 10% and the temperature rise will increase by about 20%. Therefore, when selecting the motor and the inverter, this situation should be taken into consideration, and a margin should be left to prevent the temperature rise from being too high and affect the service life of the motor.
3) If the inverter is to run with a long cable, measures should be taken to suppress the influence of the long cable to the ground coupling capacitor to avoid insufficient output of the inverter. Therefore, the inverter should be amplified by one or two gears or an output reactor at the output of the inverter.
4) For some special applications, such as high ambient temperature, high switching frequency (especially when using in buildings with high noise limit, etc.), high altitude, etc., this will cause the inverter Derating, the inverter needs to be amplified by one gear.
5) When the inverter is used to control several motors in parallel, it is necessary to consider the total length of the cable from the inverter to the motor within the allowable range of the inverter. If the specified value is exceeded, enlarge the first or second gear to select the inverter. In addition, in this case, the control mode of the inverter can only be V/F control mode, and the inverter can not realize over-current and overload protection of the motor. In this case, fuses should be added on each motor side to achieve protection.
6) When using a frequency converter to control a high-speed motor, since the reactance of the high-speed motor is small, more high-order harmonics are generated. These higher harmonics will increase the output current of the inverter. Therefore, when selecting a frequency converter for a high speed motor, it should be slightly larger than the inverter of a normal motor.
7) When the inverter is used for a pole-changing motor, pay full attention to the capacity of the inverter so that its maximum rated current is below the rated output current of the inverter. In addition, when performing the pole number conversion during operation, the motor should be stopped first, otherwise the motor will be idling, which will cause damage to the inverter.
8) When driving the explosion-proof motor, the inverter does not have an explosion-proof structure, and the inverter should be placed outside the hazardous area.
9) When using a frequency converter to drive a geared motor, the range of use is limited by the lubrication method of the rotating part of the gear. When the lubricating oil is lubricated, there is no limit in the low speed range; in the high speed range exceeding the rated speed, there is a danger that the lubricating oil will be used. Therefore, do not exceed the maximum speed tolerance.
10) When the inverter drives the wound rotor asynchronous motor, most of the existing motors are used. The winding motor has a lower impedance of the winding motor winding than a conventional squirrel cage motor. Therefore, an overcurrent trip due to ripple current is prone to occur, so select a converter that is slightly larger than the normal capacity. Generally, the winding motor is mostly used in the case where the flywheel torque GD2 is large, and more attention should be paid when setting the acceleration/deceleration time.
11) When the inverter drives the synchronous motor, it will reduce the output capacity by 10%~20% compared with the commercial frequency power supply. The continuous output current of the inverter is greater than the product of the rated current of the synchronous motor and the standard value of the synchronous pull-in current.
12) For a load with a large torque ripple such as a compressor or a vibrating machine, and a peak load with a hydraulic pump, if the inverter is selected according to the rated current or power value of the motor, overcurrent protection may occur due to the peak current. Action phenomenon. Therefore, you should understand the power frequency operation and select the inverter with a rated output current greater than its maximum current.
13) When the inverter drives the submersible pump motor, because the rated current of the submersible pump motor is larger than the rated current of the normal motor, when the inverter is selected, its rated current is greater than the rated current of the submersible pump motor.
14) When the inverter controls the Roots blower or the special blower, the Roots blower is a volumetric blower with high output wind pressure. From the perspective of the motor characteristics, its torque characteristic is approximately constant torque characteristic, and its starting current is very large, so it is necessary to pay attention to whether the capacity of the inverter is large enough when selecting the inverter.
15) When selecting a frequency converter, be sure to check whether its protection level matches the situation on site. Otherwise, dust and water on the site will affect the long-term operation of the inverter.
16) Single-phase motors are not suitable for inverter drive.
17) When the motor load is very light, even if the motor load current is within the rated current of the inverter, the inverter that is much smaller than the motor capacity cannot be used. This is because the reactance of the motor varies with the capacity of the motor. Even if the motor load is the same, the larger the motor capacity, the larger the ripple current value, and thus the current tolerance of the inverter may be exceeded.
18) If the power supply of the inverter is self-contained, it is best to add a line reactor.
16+ Years Experience Smart Watch manufacturer, ITOPNOO Provide One-stop Smart Wearable devices Solutions For You.
Our Smart Wearable products include android smart watches, Watch For iPhone, Bracelet and Wristband etc.
Leading healthcare navigation services for individuals and families who are generally healthy or face serious medical issues, and health services for employers.
The Trends New Watches Designs. Custom smart watch products designed with the vision of our clients' brands in mind.
Wholesale smart watches,Best Smart Watches,Gifts Wholesalers, smart watch manufacturer
TOPNOTCH INTERNATIONAL GROUP LIMITED , https://www.micbluetooth.com